Have any Questions?
0085225420387, 0085225420386
Get in Touch
Have any Questions?
0085225420387, 0085225420386

Products

High Energy Efficiency Cooling Solutions
Reliable & Cost Saving Cooling Systems

 

 

ETS-55W-3 and ETS-36W-2

The patented Coolsure ETS is a High Efficiency AC/DC cooling system, ideally suited for telecom access nodes and other small equipment rooms.

Substantial energy savings for new and existing sites

Substantial energy savings for new and existing sites Equipped with innovative features and high performance components, Coolsure ETS air conditioners use less than half the energy of typical comfo and precision air conditioning systems, in a package that can be deployed as a direct replacement for standard window units.

Uninterrupted active cooling during AC power failures

Coolsure ETS air conditioners offer the ultimate in cooling availability for critical telecom sites. The double-conversion DC inverter topology permits an ultra-wide input voltage and frequency range, allowing unaffected cooling operation in unstable AC mains conditions. In areas prone to complete AC mains failure, ETS can be powered efficiently from the 48V telecom backup battery via optional BCU4818 DC/DC converter, providing uninterruptible cooling and maintaining network integrity.

High availability, modular redundant cooling

The BLDC fans and compressor are operated at variable speeds eliminating the stresses of on/off regulation and extending the life of all major components. Coolsure’s patented control technology features dynamic load sharing and a sophisticated maintenance alarm system, as well as supporting N+1 redundant configurations to prevent system failure caused by unit faults.

Reduced carbon footprint without compromising network reliability

Unlike alternative cooling solutions, such as free venting and heatexchangers, Coolsure ETS air conditioners allow operators in warm climates to substantially reduce their carbon footprint without compromising on the reliability and life of the critical telecom equipment and batteries.

Technical Specifications

ModelsETS-36W-2ETS-55W-3
Cooling performance
Rated Cooling Capacity (W | BTU/hr)3600 | 122835300 | 18179
Maximum Cooling Capacity (W | BTU/hr)3800 | 129667000 | 24000
Rated input power (W)9551440
EER (W/W | BTU/hr/W)3.80 | 13.03.70 | 12.7
EER Half Load(W/W | BTU/hr/W)-5.318.2
SEER (W/W | BTU/hr/W)6.3 | 21.5-
Max ambient temperature (°C)4552
AC Mains Input
Nominal power supply (V | Hz)220-240 | 50-60220-240 | 50-60
Supply voltage range (M)160-264160-264
Starting Current--
SafetySANS 60335/IEC 60335IEC 60335
EMCSANS214/EN 55014EN 55014
DC input (requires BCU4818 DC/DC Converter)
Nominal Power Supply (Vod)48 VDC48 VDC
Supply Voltage Range (Vo)43-59 VDC43-59 VDC
Standby Current (A)<0.01<0.01
No Load Current (A)<0.5<0.5
BCU4818 Efficiency (%)> 95>95
SafetySANS 60950/IEC 60950IEC 60950
Dimensions (Evaporator | Condenser)
Dimension (WxHxD mm)910x292x205 | 754x552x2751010x315x220 | 863x602x349
Weight (kg)13 | 2613 | 33
Refrigeration Circuit
CompressorDual Rotary BLDCGMCC Rotary BLDC
Compressor ControlContinuously Variable inverterContinuously Variable inverter
RefrigerantR32R32
ConstructionCopper tubing, Aluminium finCopper tubing, Aluminium fin

UTW - 38/A

The patented Coolsure UTW is a High Efficiency AC/DC cooling system, ideally suited for telecom access nodes and other small equipment rooms.

Substantial energy savings for new and existing sites

Equipped with innovative features and high performance components, Coolsure UTW air conditioners use less than half the energy of typical comfort and precision air conditioning systems, in a package that can be deployed as a direct replacement for standard window units.

Uninterrupted active cooling during AC power failures

Coolsure UTW air conditioners offer the ultimate in cooling availability for critical telecom sites. The double-conversion DC inverter topology permits an ultra-wide input voltage and frequency range, allowing unaffected cooling operation in unstable AC mains conditions. In areas prone to complete AC mains failure, UTW can be powered efficiently from the 48V telecom backup battery via optional BCU4818 DC/DC converter, providing uninterruptible cooling and maintaining network integrity.

High availability, modular redundant cooling

The BLDC fan and compressor are operated at variable speeds eliminating the stresses of on/off regulation and extending the life of all major components. Coolsure’s patented control technology features dynamic load sharing and a sophisticated maintenance alarm system, as well as supporting N+1 redundant configurations to prevent system failure caused by unit faults.

Reduced carbon footprint without compromising network reliability

Unlike alternative cooling solutions, such as free venting and heatexchangers, Coolsure UTW air conditioners allow operators in warm climates to substantially reduce their carbon footprint without compromising on the reliability and life of the critical telecom equipment and batteries.

Technical Specifications

ModelsUTW-38/A
Cooling performance
Rated cooling capacity (W | BTU/hr)3800 | 12966
Maximum cooling capacity(W | BTU/hr)4200 | 14330
Rated input power (W)1027
EER (W/W | BTU/hr/W)3.70 | 12.6
SEER (W/W | BTU/hr/W)5.5 | 18.8
Max ambient temperature (°C)45
AC Mains input
Nominal power supply (V | Hz)220-240 | 50-60
Supply Voltage Range (M)160-264
Starting Current-
SafetySANS 60335/IFC60335
EMCSANS 214/EN 55014
DC input (requires BCU4818 DC/DC Converter)
Nominal power supply (V)48 VDC
Supply Voltage Range (Vno)43-59 VDC
Standby Current (A)<0.01
No Load Current (A)<0.5
BCU4818 Efficiency (%)>95
SafetySANS 60950/IEC 60950
Dimensions
Dimension (WxHxD mm)660x430x680
Weight (kg)42
Refrigeration Circuit
CompressorDual Rotary BLDC
Compressor controlContinuously Variable Inverter
RefrigerantR32
ConstructionCopper tubing, Aluminium fin

 

 

Coolsure ECS - 2800

The Coolsure ECS cooling system provides energy saving free cooling for BTS shelters, providing up to 90% energy savings compared to comfort air conditioners when used in cool/dry climates.

Coolsure ECS can provide the lowest Total Cost of Ownership (TCO) for Telecom operators when

Used as the sole cooling solution in cool/dry climates

Combined with Coolsure high efficiency air conditioners in climates with both hot and cool periods (eg hot days/cool nights or hot summers/cool winters)

Combined with existing low efficiency air conditioners to provide a hybrid cooling solution for existing BTS shelter sites in mostly cool, but occasionally hot climates

Used with an elevated shelter indoor temperature and humidity in hot/humid climates, where energy cost savings outweigh the cost of increased equipment failure and battery and filter replacements.

Technical Specifications

ModelECS-2800
Maximum airflow3000 m3
Cooling capacity (△T=5K)4.6 kW
Cooling capacity (△T = 7 K)6.4 kW
Cooling capacity (△T=10K)9.2 kW
Supply voltage range36-57 VDC
Nominal power consumption225 W
Nominal current draw4.4 A
Power consumption at 50% speed35 W
Fan typeEC backward curved impeller
Fan controlVariable speed
Mounting positionWall / Floor / Door
Main filter classG4/EU4 (Option: F5)
Main filter typeWashable Synthetic
Main filter surface area2.15 m2 (G4/EU4 or F5)
Pre-filter class (Optional)G2
Pre-filter typeWashable Aluminum mesh
Pre-filter surface area2.10 m2
Height607 mm
Width568 mm
Depth562 mm
Weight35 kg
Construction materialAluzinc AZ 150

 

CCU - 06

The Coolsure CCU-06 Central Control Unit is an optional item in a Coolsure High Efficiency AC/DC modular/redundant cooling system used for Coolsure cooling system communication.

Technical Specifications

CCU - 04

The Coolsure CCU-04 Central Control Unit is an optional item in a Coolsure High Efficiency AC/DC modular/redundant cooling system used for Coolsure cooling system communication.

Technical Specifications